CyberSec.Space Logo
返回 CVE 瀏覽器

CVE-2026-3611

CRITICAL
10.0
CVSS Severity Score
EPSS Score0.0070%
EPSS Percentile5.70th
Published2026年3月12日
Last Modified2026年6月5日

Vulnerability Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

Affected Platforms (CPE)

💻
Honeywell

Iq4e Firmware

< 3.30
💻
Honeywell

Iq412 Firmware

< 3.30
💻
Honeywell

Iq422 Firmware

< 3.30
💻
Honeywell

Iq4nc Firmware

< 3.30
💻
Honeywell

Iq41x Firmware

< 3.30

References & Advisories